Circuit breaker, ComPact NS1250N, 50kA/415VAC, Micrologic 2.0 trip unit, 3P 1250A, FIX
| Specifications | 
| Range | ComPact NS | 
| Country of Origin (Estimated) | China | 
| Warranty | 12 months | 
| CO/CQ | Yes (if) | 
| Product name & Device short name | Compact NS1250N | 
| Device application | Distribution | 
| Poles description | 3P /4P | 
| Protected poles description | 3P 3d /4P 4d | 
| [In] rated current | 1250 A at 40 °C | 
| Network type | AC | 
| [Ue] rated operational voltage | 690 V AC 50/60 Hz | 
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 | 
| Trip unit name | MicroLogic 2.0 A | 
| Trip unit technology | Electronic | 
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings | 
| Trip unit rating | 1250A | 
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In | 
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz | 
| Connection pitch | 70 mm | 
| Breaking capacity [Icu] | 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 
| [Ics] rated service breaking capacity | 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Mechanical durability | 10,000 cycles | 
| Electrical durability | 4000 cycles at 440 V In | 
| Protection type | L : for overload protection (long time) I : for instantaneous short-circuit protection | 
Dimensions (mm) (HxWxD) | 3P /327x210x147 mm 4P/327x280x147 mm | 
| Net weight (Kg) | 3P/14Kg 4P/18Kg | 
| Door cutout Dimensions (XxY) | 3P/194x216 mm 4P/244x216 mm |